ASTM E2257墻壁和天花板材料和組件的房屋著火試驗的標準試驗方法

放大字體  縮小字體 發布日期:2012-02-08   瀏覽次數:45  分享到: 分享到騰訊微博
ASTM E2257墻壁和天花板材料和組件的房屋著火試驗的標準試驗方法
ASTM E2257 Standard Test Method for Room Fire Test of Wall and Ceiling Materials and Assemblies
ASTM E2257墻壁和天花板材料和組件的房屋著火試驗的標準試驗方法

This fire test is applicable to a description of certain fire performance characteristics in appraising wall and ceiling materials, products, or systems under specified fire-exposure conditions in an enclosure. The test indicates the maximum extent of fire growth in a room, the rate of heat release, and if they occur, the time to flashover, and the time to flame extension beyond the doorway following flashover. It determines the extent to which the wall and ceiling materials or assemblies contribute to fire growth in a room and the potential for fire spread beyond the room, under the particular conditions simulated. It does not measure the contribution of the room contents. (See Appendix X1, Commentary.)
Note 1—Time to flashover is defined herein as either the time when the radiant flux onto the floor exceeds 20 kW/m2 or the average temperature of the upper hot gas layer reaches 600°C (1100°F) or flames exit the doorway or spontaneous ignition of a paper target on the floor occurs. The spontaneous ignition of a crumpled single sheet of newspaper placed on the floor 0.9 m (3 ft) out from the center of the rear wall provides a visual indication of flashover.
The potential for the spread of fire to other objects in the room, remote from the ignition source, is evaluated by measurements of: (a) the total heat flux incident on the center of the floor, and (b) a characteristic upper level gas temperature in the room.
The potential for the spread of fire to objects outside the room of origin is evaluated by the measurement of the rate of heat release of the fire.
Measurements of the rate of production of carbon monoxide, carbon dioxide, and visible smoke are taken.
The overall performance of the test specimen is visually documented by full-color photographic records. Video taping of the complete fire test is an acceptable alternative to the photographic record. Such records show when each area of the test specimen becomes involved in the fire.
In this procedure, the specimens are subjected to a specific set of laboratory fire test exposure conditions. If different test conditions are substituted or the anticipated end-use conditions are changed, it is not known whether it is possible by use of this test to predict changes in the performance characteristics measured. Therefore, the results are strictly valid only for the fire test exposure conditions described in this procedure.
1. Scope
1.1 This is a fire-test-response standard.
1.2 This test method is intended to evaluate, under specified fire-exposure conditions, the contribution to room fire growth provided by wall or ceiling materials and assemblies, or both. The method is not intended to evaluate the fire endurance of assemblies or fires originating in the wall assembly. The method provides a means to evaluate the effectiveness of thermal barriers in restricting the contribution of combustible materials in the wall assembly to fire growth in a room fire.
1.3 This test method, simulating a fire in the corner of a 2420 by 3630 mm (8 by 12 ft) room containing a single open doorway, provides a means to evaluate the relative performance of specified wall and ceiling materials or assemblies when they are used together in the same relationship within an enclosure, and simulating the manner in which they will be used.
1.4 This test method is intended to evaluate the contribution to fire growth provided by a surface product using a specified ignition source. It shall, however, be noted that the type, position and heat output of the ignition source will considerably influence fire growth. The thermal exposure conditions from the ignition source specified in this method will result in flashover during the 20 min duration for many common finish materials, in particular if specimens are mounted on the walls and the ceiling (standard configuration).
1.5 This test method provides a means for evaluating wall and ceiling finish materials and assemblies, including panels, tiles, boards, sprayed or brushed coatings, etc. This test method is not intended to evaluate flooring materials or furnishings.
1.6 This method shall be used in conjunction with Guide E 603, which covers instrumentation and the general effect of various parameters, and Guide E 2067, which deals with full-scale oxygen consumption calorimetry.
1.7 The values stated in SI units are to be regarded as the standard. The units given in parentheses are for information only.
1.8 The text of this standard references notes and footnotes which provide explanatory information. These notes and footnotes (excluding those in figures) shall not be considered as requirements of the standard.
1.9 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire-hazard or fire-risk assessment of the materials, products, or assemblies under actual fire conditions.
1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.

2. Referenced Documents (purchase separately)
ASTM Standards
E84 Test Method for Surface Burning Characteristics of Building Materials
E136 Test Method for Behavior of Materials in a Vertical Tube Furnace at 750C
E176 Terminology of Fire Standards
E603 Guide for Room Fire Experiments
E2067 Practice for Full-Scale Oxygen Consumption Calorimetry Fire Tests
ISO Standards
ISO13943 Fire Safety--Vocabulary
NFPA Standards
NFPA286 Standard Method of Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth
Index Terms
carbon dioxide; carbon monoxide; corner; fire; fire-test response; flame; heat release; heat release rate; ignition; optical density; oxygen consumption calorimetry; room; smoke obscuration; toxic gases; Ceiling suspension systems; Fire testing--building materials; Room fire testing; Wall construction;
 

  詳情請咨詢
  防火資源網-阻燃防火測試中心
  電話:(+86)0592-5056213
  傳真:(+86)0592-5105807
  郵件:firetest@firetc.com

凡注明"防火資源網"的所有作品,由<防火資源網>整理編輯,任何組織未經<防火資源網>及其擁有者授權,不得復制、轉載、摘編或利用其它方式應用于任何商業行為。

 
 
[ 防火測試中心搜索 ]  [ ]  [ 告訴好友 ]  [ 打印本文 ]  [ 關閉窗口 ]  [ 返回頂部 ]

 

 
 
推薦防火測試
推薦圖文
點擊排行
 
 
網站首頁 | 廣告服務 | 關于我們 | 聯系方式 | 服務協議 | 版權聲明 | 網站地圖 | 友情鏈接 | 網站留言 | 舊版本 | 閩ICP備09009213號
?2019-2021 FIRETC.COM All Rights Reserved ? 備案號:閩ICP備09009213號-1在線客服 點擊QQ交談/留言 點擊QQ交談/留言
主站蜘蛛池模板: 246天天好彩免费资料大全下载 | 新澳门六开彩开奖结果2025年 | 天下彩正版资料正常进入app免 | 澳门六开彩资料免费大全今天 | 2025最新版水果奶奶下载安装 | 香港内部精准资料 | 澳门香港开奖结果2025开奖记录 | 香港资料大全正版资料2025 | 2025澳门国际龙舟赛 | 最新澳门6合开彩开奖结果查询 | 正版香港资料第一版香港正版免费 | 2025年生肖马运势大全图表 | 2025香港图库免费 | 香港宝典图库图 | 4949精准澳门彩最准确的 | 118彩图库主图最新版v1.49.77 | 20250161期今晚买四不像必中一肖图 | 白小姐一期一肖一资料 | 彩库宝典下载香港正版资料 | 一码一肖管家婆中奖率高达100% | 494949今晚最快开奖现场直播 | 管家婆一奖一特一中 | 管家婆三期内必开一期的优缺点 | 新澳门金牛版正版新澳门 | 管家婆一笑一码100正确 | 新澳最新快资料王中王 | 惠泽社群,澳门正版资料 | 澳门一码一肖100准今期指点 | 刘伯温白小姐期期准准 | 111153金光佛论坛,香港赛马会 | 今晚特马会出几号啊2025 | 2025年一码一肖100精准 | 2025年新澳门全年免费资料大全 | 白小姐三肖三码必中一期 | 2025香港历史记录 | 澳门免费资料大全49 | 香港数据中心市场规模将突破40亿美元 | 2025年正版资料免费大全 | 澳门今天晚上买什么好——精选解释解析落实 | 香港数据中心市场规模将突破40亿美元 | 777778888精准管家婆 |